Monday, December 14, 2015

December 14, 2015

Common Tests Performed on Transformers

If you are involved in transformer (oil immersed) maintenance in your company, here is a list of common tests required to be done on oil immersed transformers according to IEC 60076-1 :

Routine Tests
Measurement of winding resistance
Measurement of voltage ratio and check of phase displacement
Measurement of short-circuit impedance and load loss
Measurement of no-load loss and current
Dielectric routine tests
Tests on on-load tap-changers, where appropriate

Special Tests
Dielectric special tests
Determination of capacitances windings-to-earth, and between windings
Determination of transient voltage transfer characteristics
Zero-sequence impedance(s) on three-phase transformers
Short-circuit withstand test
Determination of sound levels
Measurement of the harmonics of the no-load current
Measurement of the power taken by the fan and oil pump motors
Measurement of insulation resistance to earth of the windings, and/or measurement of dissipation factor (tan d) of the insulation system capacitances

Type Tests
Temperature-rise test
Dielectric type tests
December 14, 2015

Transformer Name plate � What information is required

Transformers are usually provided with a rating plate of weatherproof material situated in a visible position. All entries on the plate are usually indelibly marked. According to the IEC 60076-1 standard for transformers, the following are the minimum information required for a transformer name plate. If you are involved in specifying transformers, purchasing transformers or work with transformers, here is a checklist for typical transformer name plate information:

Oil Filled Transformers Name Plate Information:
Kind of transformer
Number of the applied standard
Manufacturer�s name
Manufacturer�s serial number
Year of manufacture
Number of phases
Rated power (kVA or MVA)
Rated frequency (Hz)
Basic insulation levels
Rated voltage and tapping range (V or kV)
Rated currents (A or kA)
Connection symbol
 Short-circuit impedance (%)
Type of cooling
Total mass
Mass of insulating oil

Additional Information Required for Dry-Type Transformers
Temperature class
Climatic class
Environmental class
Fire behavior class
Degree of protection (IP class)
December 14, 2015

How Transformers are Cooled

Increasing the cooling rate of a transformer increases its capacity to handle more power requirements. Various methods exist for cooling oil immersed industrial transformers to guarantee efficient operation. Cooling methods must not only maintain a sufficiently low average temperature, but must prevent an excessive temperature rise in any portion of the transformer. It must prevent hot spots within the transformer. For this reason, working parts of large transformers are usually submerged in high-grade insulating oil. This oil must be kept as free as possible from moisture and oxygen, dissolved combustible gases, and particulates

Transformer Cooling Methods
The efficiency of the cooling is a crucial factor determining the operational safety and the life span of a transformer. Below are the four common cooling methods for industrial transformers. Each method is illustrated with a diagram:

(a) Natural air cooling with radiators (ONAN)
(b) Radiators additionally cooled by fans (ONAF)
(c) Cooling by separate radiator banks
(d) Water as cooling medium

Monday, August 4, 2014

August 04, 2014

Instrument Transformers � Basic Operating Principles

Instrument transformers are used for measuring and control purposes. They provide currents and voltages proportional to the primary, but there is less danger to instruments and personnel.

There are two distinct classes of instrument transformers: the potential transformer and the current transformer. 
Potential transformers (PTs) are used to step down high voltage while current transformers (CTs) used to step current down. The function of a PT is to accurately measure voltage on the primary, while a CT is used to measure current on the primary.

Potential Transformer
Potential (voltage) transformers have primary and secondary windings on a common core:
Schematic of a Potential Transformer & Symbol in electrical circuit
Standard potential transformers are single-phase and are usually designed so that the secondary voltage maintains a fixed relationship with the primary voltage. Potential transformers are used with voltmeters, wattmeters, watt-hour meters, power-factor meters, frequency meters, synchroscopes and synchronizing apparatus, protective and regulating relays, undervoltage and overvoltage trip coils of circuit breakers.

Generally, a potential transformer is designed to be connected in parallel with the lines to transform and step down the line voltage to 115 or 120 volts for metering or relay operation. They are typically rated 50 to 200VA (volt-amperes) at 120 secondary volts. The secondary terminals should never be short circuited because a heavy current will result, which can damage the windings.

Current Transformers
A current transformer transforms line current into values suitable for standard protective relays and instruments.  The primary of a current transformer has a  few turns, while the secondary may have a great many turns which results in the stepping down of current as shown in the schematic below:

Current Transformer schematic & Symbol in electrical circuit
Current transformers are used with ammeters, wattmeters, power factor meters, watt-hour meters, compensators, protective and regulating relays, and trip coils of circuit breakers. The secondary of current transformers are typically rated 5Amps.
Most times, current transformers have several taps on the secondary winding to adjust the range of current possible to measure on the primary.

Note if the secondary of a current transformer is opened, an extremely high voltage is induced in the secondary which is dangerous to personnel and can destroy the current transformer. For this reason, the secondary of a current transformer should always be shorted before removing a relay from its case or removing any other device that the current transformer operates. This protects the current transformer from overvoltage.

Sunday, August 3, 2014

August 03, 2014

What are Autotransformers?


Transformers having only one winding are called autotransformers. This is the most efficient type of transformer since a portion of the one winding carries the difference between the primary and secondary currents.

An autotransformer has the usual magnetic core like a typical transformer but only one winding, which is common to both the primary and secondary circuits. An autotransformer schematic is shown below:

Autotransformer Schematic
The primary is always the portion of the winding connected to the AC power source. This transformer may be used to step voltage up or down. If the primary is the total winding and is connected to a supply, and the secondary circuit is connected across only a portion of the winding (as shown in schematic (a) above), the secondary voltage is �stepped-down.�  If only a portion of the winding is the primary and is connected to the supply voltage and the secondary includes all the winding(as shown above in schematic (b) above) then the voltage will be �stepped-up� in proportion to the ratio of the total turns to the number of connected turns in the primary winding.

The main disadvantage of the autotransformer is that the primary and secondary
circuits are electrically connected and, therefore, could not safely be used for stepping down from high voltage to a voltage suitable for plant loads.

Uses of the Autotransformer
Autotransformers find wide application in the following situations:
(a) Where the system supplied contains an identified-grounded conductor that is solidly connected to a similar identified grounded conductor of the system supplying the autotransformer.
(b) Where an induction motor is to be started or controlled
(c) Where a dimming action is required, as in the theatre lighting
(d) Where the autotransformer is to be a part of a ballast for supplying lighting units

Saturday, August 2, 2014

August 02, 2014

NEMA Insulation Classes for Transformers

The capacity or rating of a transformer is limited by the temperature that the insulation can tolerate.  The life of a transformer can be extended by making sure it is not operated over and above the temperature rating of the insulation system on a continuous basis. A guiding rule of thumb would be that the useful operating life of the transformer halves for every 10�C  rise above its rated temperature. 

The insulation system of a transformer is rated in degrees Celsius at its maximum temperature rating:

The class number  = the maximum �C of the transformer insulation

NEMA (National Manufacturer�s Association) has the following thermal or insulation classification as regards transformers (dry type):


NEMA Insulation Class
NEMA Letter Designation
Ambient
Temperature
Maximum Allowable Temperature Rise
Maximum Allowable Operating Temperature
�C 
�F
�C 
�F
105
A
40�C 
50
122
105
221
130
B
80
176
130
226
155
F
105
221
155
311
180
H
125
257
180
356
220
R
150
302
220
428

Note  that a transformer with a Class 220 insulation system can be designed for a maximum temperature rise that is lower than the standard 150�C . It can be designed for either 125 or 80�C rise. Also, a Class 180 insulation transformer can be designed with 80�C rise. Class 155 and 105 transformers are not typically designed for other than their standard temperature rise

The maximum operating temperature is determined by by adding the rated ambient temperature of the device which is normally 40�C, the maximum temperature rise, and a 10�C hot-spot allowance:
Maximum operating Temperature 
= Ambient Temperature + Maximum Temperature Rise + 10�C hot-spot allowance.

August 02, 2014

Basics of Transformer Ratings

Transformers are rated using several methods. Two common ratings of transformers include the:
(a) KVA rating
(b) Impedance rating

KVA Rating
KVA ratings of transformers are obtained by simply multiplying the current times the voltage. The result is a rating in VA or volt amperes. Small transformers are rated in VA. As size increases, the ratings are adjusted accordingly to KVA (kilovolt amperes) or MVA (megavolt amperes)
1KVA = 1,000VA or volt amperes
1MVA = 1,000,000VA
Power transformers are defined as transformers rated 500 kVA and larger. Transformers smaller than 500 kVA are generally called distribution transformers.


Impedance Rating
The impedance of a transformer is the total opposition offered to an alternating current. When referring to impedance of a transformer, it is the equivalent impedance that is meant. To determine the equivalent impedance of a transformer, one of the windings, usually the low voltage winding is short circuited while just enough voltage is applied to the other winding to create full load current in the short circuited winding. This voltage is known as the impedance voltage.

Impedance rating is a characteristic of large power and distribution transformers. The transformer impedance value is often given in percent on the nameplate
It means that the voltage drop due to the impedance is expressed as a percent of rated voltage.
For example, suppose the impedance rating of a 2400V/240V transformer with full load current of 90 amps is given as 3%. 
Voltage drop due to impedance with low voltage winding short circuited 
= 0.03 X 2400 = 72volts
This means there would be a 72-volt drop in the high-voltage winding at full load due to losses in the windings and core. Only 1 or 2% of the losses are due to the core; about 98% are due to the winding impedance.


We can also calculate the actual impedance value on the high voltage side in ohms:

Where:
Z = impedance in ohms
V = impedance voltage drop
I =  Rated full load current in the primary of transformer

Now V = 72V, I = 90Amp
Therefore Z = 72/90 = 0.8?

Thursday, July 31, 2014

July 31, 2014

How a Voltage Transformer Works

Transformer function is based on the principle that electrical energy is transferred efficiently by magnetic induction from one circuit to another. Basically, a transformer consists of two or more windings placed on the same magnetic path. The winding being fed electrical energy is called the primary winding while the winding where the load is connected is called the secondary winding. A typical two winding transformer action is shown below:
Transformer Action
When the primary winding of a transformer is energized from an alternating current (AC) source, an alternating magnetic field is established in the transformer core. Alternating magnetic lines of force, called �flux,� circulate through the core. With a second (secondary) winding around the same core, a voltage is induced by the alternating flux lines. A load, connected to the terminals of the secondary winding, results in current flow.

Parts of A Transformer
A transformer is made up of two basic non-moving parts:
(a) A laminated iron core
(b) Windings (primary & secondary)

Laminated Iron core
The iron core of a transformer is made up of sheets of rolled iron. This iron is treated so that it has a high magnetic conducting quality (high permeability) throughout the length of the core. Permeability is the term used to express the case with which a material will conduct magnetic lines of force. 
The iron also has a high ohmic resistance across the plates (through the thickness of the core). It is necessary to laminate the iron sheets to reduce heating of the core. There are two common types of transformer cores:
(a) Core type
(b) Shell type

Core and Shell type transformers
In the core-type (core form) transformer, the windings surround the core. In a shell-type (shell form) transformer, the steel magnetic circuit (core) forms a shell surrounding the windings. In a core form, the windings are on the outside; in a shell form, the windings are on the inside.

Windings
A transformer has two windings; the primary winding and the secondary winding. 
The primary winding is the coil which receives the energy.  It is formed, wound and fitted over the iron core. The secondary winding is the coil, which discharges the energy at a transformed or changed voltage.

Types of Transformers
Transformers are classified according to different criteria. However here is a list of the more common generic types of transformers:
(a) Single phase transformers
(b) Three phase transformers
(c) Potential or voltage transformers
(d) Autotransformers
(e) Current transformers
(f) Power transformers

Voltage Ratio of a Transformer
The voltage on the windings of a transformer is directly proportional to the number of turns on the coils of the windings. This relationship is expressed by the formula:

Voltage ratio of a transformer
Where:
Vp = voltage on primary coils, V
Vs = voltage on secondary coils, V
Np = number of turns on primary coils
Ns = number of turns on secondary coils

The ratio Vp / Vs is called the voltage ratio (VR). The ratio Np / Ns is called the turns ratio (TR). 

A voltage ratio of 1:4 (read as 1 to 4) means that for each volt on the transformer primary, there is 4V on the secondary. When the secondary voltage is greater than the primary voltage, the transformer is called a step-up transformer.

A voltage ratio of 4:1 means that for each 4V on the primary, there is only 1V on the secondary. When the secondary voltage is less than the primary voltage, the transformer is called a step-down transformer.

Current Ratio
The current in the coils of a transformer is inversely proportional to the voltage in the coils. This relationship is expressed by the equation:

current ratio of a transformer

Where:
Ip = current in primary coil, A
Is = current in secondary coil, A

In the equation above we may substitute Np / Ns for Vp / Vs so we have:

Transformer Efficiency
The efficiency of a transformer is equal to the ratio of the power output of the secondary winding to the power input to the primary winding.
An ideal transformer is 100 percent efficient because it delivers all the energy it receives.  
However, because of core and copper losses, the efficiency of even the best practical transformer is less than 100 percent. Expressed as an equation:
Transformer Efficiency
Where: 
Eff = efficiency
Ps  = power output from secondary = Input power �core losses � Copper losses
Pp  = power input to primary

Efficiencies of well-designed transformers are very high, averaging over 98 percent (%) for power transformers. The only losses, in a transformer, are due to core losses which go to maintaining the alternating magnetic field, resistance losses in the coils, and power used for cooling for large transformers requiring cooling. 

The main reason for high efficiencies of transformers, compared to other equipment, is the absence of moving parts. Transformers are called static AC machines.