Monday, October 2, 2017

October 02, 2017

How to Test a 3 Phase Motor Windings With an Ohmmeter

Every 3 phase motor has six (6) terminals with the supply voltage connected to three (3) of those terminals. The most common configuration of a three-phase  motor is the Delta (?) � Star (Wye) configuration with the Delta side connected to supply voltage. The terminal configuration of a 3 phase motor is shown below:

Terminals Configuration of a 3 Phase Motor
The W2U2V2 terminal set is the star side of the 3 phase motor while the U1VIW1 is the Delta side of the motor connected to the supply voltage.

The 3 phase motor is a rugged piece of equipment but as with everything man made, there comes a time when this beautiful piece of machinery fails either due to old age, misapplication, mal-operation or any other adverse cause.

The most common failure mode of a 3 phase AC motor is burnt winding or shorted winding leading to the damage of the motor. Often it is required to test the winding of the 3 phase windings with the aid of a multimeter or ohmmeter to determine whether the motor is still good or burnt or shorted.

How to Test the Winding of a 3 phase Motor

To determine whether a 3 phase motor is still good or has gone bad, a simple ohmmeter test across the windings of the motor will reveal its true state of health. As shown below, the indicated terminal matrix (blue lines) shows the way the windings of a 3 phase motor should be tested with an Ohmmeter:
How to test the windings of a 3 Phase Motor with an Ohmmeter

The first thing to do before testing the windings of the motor is to remove the links linking terminals W2U2V2 and the disconnect the motor from supply (L1, L2, L3). A multimeter terminals placed across this matrix of terminals will indicate the following readings for a good 3 phase motor:
(a) Terminals W1W2, U1U2, V1V2 will indicate continuity for a good motor
(b) Every other terminal combinations should indicate Open for a good motor
(c) Readings between any of the six (6) terminals and the motor frame signifying earth     
    (E) should indicate open for a good motor.

Ohmmeter Readings for a Bad 3 phase Motor

In the case of a burnt or bad 3 phase motor, this matrix of terminals should indicate  the opposite readings for a bad motor:
(a) If any of the terminal combinations W1W2, U1U2, V1V2 should indicate open then 
     the motor is bad.
(b) If any other terminal combinations should indicate continuity instead of open, then            
     the motor is bad.
(c) If the reading between any of the six (6) terminals and motor frame (E) should  
     indicate continuity, then the motor is dead.


October 02, 2017

Electric Motor Specifications for Hazardous Locations

A hazardous environment or location is some combustible materials that could easily ignite and create a fire hazard. Electric motors operated in such an environment need to be carefully specified and selected in order not to pose an explosion threat to an installation.

Arcs, sparks and high temperatures on the surfaces of electric motors are common sources of ignition of hazardous substances. Therefore the right motors need to be specified and selected for use in this kind of environments otherwise the consequences of an explosion and eventual fire resulting from using the wrong kind of motor could range from minor injuries, production down time and destruction of valuable investment as well as death.

Information Required to Specify an Electric Motor for Use in Hazardous Locations

Four basic information are required to specify and select the right motor for use in a hazardous environment:
1. Class of materials in the hazardous environment
2. Division classification of the hazardous environment
3. Group classification of the hazardous environment
4.     The autoignition temperature (AIT) of the hazardous material in the environment
How to Select Electric Motors for Use in Hazardous Locations

Class of Materials in the Hazardous Environment.

There are three classes of hazardous locations according to the NEC and CEC:


Class Location Hazardous Materials Present
         I Contains flammable gases or vapors e.g Hydrocarbon gases
         II Contains dusts either electrically conductive or explosive in air
        III Contains filings and flyings that are easily ignitable e.g texile industry 

*NEC -  National Electric Code
*CEC -  Canadian Electrical Code

Division of the Hazardous Environment

Division describes the condition under which the hazardous material is present in the particular environment. There are two basic divisions: Division 1 and Division 2 locations

Division 1 Location
A Division 1 location is one where an explosive or ignitable material is present under normal operating condition. Division 1 locations include environment where explosive materials are routinely exposed to the environment during regular operation and scheduled maintenance.


Division 2 Location
A Division 2 location is one where hazardous substances are stored or handled under abnormal conditions.


Group Classification of Hazardous Environment.

Class I and Class II are divided into groups according to the behaviour of the hazardous material after it has been ignited. These groupings are shown below:
Class Location Groups 
                        I A, B, C, D
                       II E, F, G

Autoignition Temperature of Hazardous Materials

A key information required to accurately specify an electric motor in a hazardous environment is the autoignition temperature of the hazardous material, AIT for short.

The AIT refers to the minimum temperature at which there is sufficient energy for a hazardous material (chemical) to ignite spontaneously in the absence of a spark, flame or other source of ignition. The AITs of various Class I and Class II hazardous materials are shown in the table below:

*Class Group Hazardous Material
Autoignition Temperature
�C�F
     I        A  Acetylene
 305
581
      B Butadiene
420
788
Ethlylene Oxide
570
1,058
Hydrogen
500
932
     C Acetaldehyde
175
347
Cyclopropane
498
928
Diethyl Ether
180
356
Ethylene
450
842
Isoprene
398
743
    D Acetone
465
869
Amonia
651
1,204
Benzene
498
928
Butane
287
550
Ethane
472
882
Ethanol
363
685
Gasoline
246 - 280
475 - 536
Methane
537
999
Propane
450
842
Styrene
490
914
   II    E Aluminium
650
1,202
Bronze
370
698
Chromium
580
1,078
Magnesium
620
1,148
Titanium
330
626
Zinc
630
1,166
   F Coal
610
1,130
   G Corn
400
752
Nylon
500
932
Polyethylene
450
842
Sugar
350
662
Wheat
480
896
Wheat Flower
380
716

*Source : American Institute of Chemical Engineers (AIChE) - www.aiche.org

Characteristics of Motors in Class I, Division 1 & 2 Hazardous Locations

To be able to apply an electric motor successfully in a hazardous environment, these motors must possess certain critical characteristics that make them suitable to operate in these environment without creating problems.
  1. These motors must be built and labelled as explosion-proof
  2. An explosion-proof motor must contain an internal explosion without rupturing
  3. An explosion-proof motor must have flame paths for exhausting hazardous gases during an explosion and for cooling the hazardous material as they leave the motor to prevent further explosion.
  4. The more severe the explosion hazards, the stronger the enclosures of the motor and the longer the flame paths. For example, motors for use in group A environment which has acetylene gas require the highest enclosure strength and longest flame paths compared with those used in group D environment with only propane gas.
  5. Motors for use in hazardous environment are assigned a temperature code (T-Code), an identification number which describes the maximum temperature of surfaces subject to contact with hazardous materials. The temperature value defined by the T-code applies under all conditions of motor operation including burnt out, overload and locked rotor current.
  6. The T-code for a given motor must be less than the AIT of the hazardous gas or mixture in the environment where the motor operates. This is to ensure that the hazardous materials do not spontaneously ignite when it contacts the motor surfaces and enclosure during operation.

Temperature Codes of Motors Operating in Hazardous Locations According to NEC, CEC & IEC Designations:

The table below gives the temperature codes for motors operating in hazardous environment according to NEC/CEC  & IEC letter designations are given in the table below:


**NEC/CEC
Designation
T - Code
IEC
Designation
T - Code
Maximum Surface Temperature
�C
�F
T1
T1
450
842
T2
T2
300
572
T2A

280
536
T2B

260
500
T2C

230
446
T2D

215
419
T3

200
392
T3A
T3
180
356
T3B

165
329
T3C

160
320
T4
T4
135
275
T4A

120
248
T5
T5
100
212
T6
T6
85
185
   
 **Source : American Institute of Chemical Engineers (AIChE) - www.aiche.org

Class I, Division 2 Motors

The minimum requirements for motors for use in Class I, Division 2 locations are less stringent than those for use in Class I, Division 1 locations. Some basic characteristics and requirement for motors for use in Class I, Division 2 locations are enumerated below:
  1. An explosion-proof motor certified for use in a Class I, Division 1 location may also be operated in a Class I, Division 2 area provided the motor meets the group and T-Code requirements.
  2. TEFC (Totally Enclosed, Fan Cooled) motors and ODP (Open Drip -proof) motors can be used in Division 2 locations provided they do not have ignition sources such as arc-producing brushes or switching mechanisms.
  3. Three-phase induction motors with low surface temperatures and no sparking parts can be used in Division 2 locations.

Characteristics of Motors for use in Class II locations
  1. As class II locations contain ignitable dusts, electric motors operating in this kind of environment must be dust-ignition-proof.
  2. The enclosures of dust-ignition-proof motors are designed to exclude hazardous materials from accessing the internals of the motors unlike explosion-proof motors.
  3. The T-code of a dust-ignition-proof motor must correspond to a maximum surface temperature below the AIT of the hazardous dust materials.

Nameplate Requirements for Motors Operating in Hazardous Locations

Selecting the right kind of motor that meets the requirements for use in hazardous environment is not an easy task. However, manufacturers of electric motors for use in hazardous locations have standard nameplates that contain the following information:
(a) Type of Enclosure of Motor
(b) Class of hazardous materials for which the motor is suitable
(c) Group of the hazardous materials 
(d) T-code of the electric motor

The above information makes it less tedious in selecting and specifying a motor for use in a hazardous environment.


Thursday, December 22, 2016

December 22, 2016

Checklist for Selecting and Order an Electric Motor

The two most important factor to consider when selecting an electric motor are:
1. The electricity supply to which the motor will be connected - AC or DC. If AC three phase or              single phase.
2. Type of enclosure or housing

Type of Electric Motor Enclosure
There are two basic enclosure options available:  drip proof in steel or totally enclosed, in aluminium, steel and cast iron.
The totally enclosed fan cooled (TEFC) motor is the predominant standard for industrial applications, today. The versatile TEFC is fully enclosed within the motor frame, with cooling air directed over it by an externally mounted fan.

Other Key Factors Required for Motor Selection
Loading (KW)
Loading is determined by the equipment to be driven, and the torque available at the shaft. Electric motors have standard outputs per frame size from which any KW loading required can be selected from.

Speed
Choose the required speed of the motor. The induction motor is a fixed single speed machine. Its speed is dependent on the frequency of the electricity supply and the stator winding design. The no load speed of an induction motor is slightly lower than synchronous speed due to the no load losses in the machine. Full load speed is typically a further 3-4 per cent lower than no load speed.

Mounting
The mounting position must always be given when a motor is to be selected. Improper motor mounting can affect performance.

Power Supply
The supply voltage and frequency must be given when selecting an Electric motor

Operating Environment
This is one of the major factors that affect motor performance. The environment in which the motor is to operate is an important factor to consider when selecting a motor, as the ambient temperature, humidity and altitude can all affect performance

Checklist for Ordering a Fixed Speed TEFC Motor:
1. Power Supply Voltage (Volts) No. of Phases  Frequency (Hertz)

2. Power Rating  KW

3. Speed Rev/min  No. of Poles

4. Duty Type Mounting IM

5. Motor Drive Direct Belt

6. Insulation Class/Temperature Rise Insulation Class Temperature Rise (oC)

7. Torque Type Quadratic Constant

8. Environmental Conditions IP Rating Ambient Temperature (oC)Relative Humidity


Checklist for Ordering a TEFC Variable Speed Electric Motor
1. Power Supply Voltage (Volts) No. of Phases  Frequency (Hertz)

2. Power Rating  KW

3. Speed Rev/min  No. of Poles

4. Duty Type Mounting IM

5. Motor Drive Direct Belt

6. Insulation Class/Temperature Rise Insulation Class Temperature Rise (oC)

7. Torque Type Quadratic Constant

8. Environmental Conditions IP Rating Ambient Temperature (oC)Relative Humidity

9. Variable Speed Drive Specifications
a. Type of Controller Direct Torque Control (DTC) Pulse Width Modulation (PWM)
b. Speed Range Maximum Rev/min Minimum Rev/min
c. Absolute Power (KW) Maximum (KW) Minimum (KW)
d. Output Fitters Fitted Non-Fitted
e. Maximum Cable Length (Meters) Cable length (m)


December 22, 2016

Electric Motor Standards as Defined By the IEC and the Harmonized European Standard

Are you working with electric motors or there is the need to specify motors and you need to know what standard applies to what area of electric motors? The table below will be of great help as it itemizes the basic standards that define all areas of electric motor design, construction and installation:

International Standard IEC
Harmonized European Standard
Description
IEC 60034-1 +A1 and A2 EN 60034-1+A1, A2 and All Rotating electric motors. Part 1: Rating and design
IEC 60034-2+A1, A2 and IEC 60034-2A EN 60034-2 + A1 and A2 Rotating electric motors. Part 2: Measuring methods to determine the loss and the efficiency of electric motors (except machines for traction vehicles)
IEC 60034-5 EN 60034-5 Rotating electric motors. Part 5: Enclosure class for rotating electric motors.
IEC 60034-6 EN 60034-6 Rotating electric motors. Part 6: Cooling (IC code)
IEC 60034-7+A1 EN 60034-7+A1 Rotating electric motors. Part 7: Classification of types of construction and mounting (IM code)
IEC 60034-8 EN 60034-8 Rotating electric motors. Part 8: Terminal marking and direction of rotation
IEC 60034-9 EN 60034-9 Rotating electric motors. Part 9: Noise limits
IEC 60034-11 - Thermal protection
IEC 60034-12 EN 60034-12 Rotating electric motors. Part 12: Start capacity of three-phase induction motors.
IEC 60034-14 EN 60034-14 Rotating electric motors. Part 14: Mechanic vibration for machines with drive shaft heights of 56mm or more. Measuring, estimate and vibration limits
IEC 60038 - IEC Standard Voltages.
IEC 60072-1 EN 50347 Dimensions and output power for rotating electric motors. Part 1: Frame size 56 to 400 and flange size 55 to 1080.
IEC 62114 - Electrical insulation systems
- EN 50102 Degrees of protection for enclosures for electrical equipment against external mechanic strokes. (IK-code)
IEC 60072-1 EN 50347 Three-phase induction motors for standard use with standard dimensions and output power. Frame size 56 to 315 and flange size 65 to 740.
Other Standards
DIN 51825
Lubricant; lubricating grease k; classification and requirement (1990-08)
DIN 44082
Thermistors; PTC sensors; thermal protection of machines; climate categorization HFF (1985 -06)
ISO 2409 EN ISO 2409 Paints and enamels. Grid cut value.
- EN ISO 3743-2 Definition of sound power level. Minor removable sources of noise. Engineering method. Part 2: Rooms with sound control
- EN ISO 4871 Declaration and verification of noise from machines and equipment.
- EN ISO 11203 Noise from machines and equipment. Measurement of sound pressure by the operator's ear (noise emission). Calculation on the basis of sound power level.



Wednesday, December 21, 2016

December 21, 2016

Common Ingress Protection (IP) Ratings for Electric Motors

Enclosures of electrical equipment, per characteristics where they will be installed and their maintenance accessibility, should offer a certain degree of Protection also known as Ingress Protection (IP). Standard IEC 60034-5 defines the degrees of protection of electrical equipment by means of the characteristic letters IP, followed by two characteristic numerals. NEMA also defines IP ratings for enclosures. Read IEC Ingress Protection Ratings.  Read also : NEMA Ingress Protection Ratings 

The IEC and NEMA IP ratings are defined for all spectrum of equipment used in an environment where dust, particles, water etc can compromise their performance. However specifically for motors, the standards define the below listed commonly used IP ratings such that there can be no misinterpretation:

Motor
Degree of Protection
First Characteristic Numeral
Second Characteristic Numeral
Protected Against Accidental Contact
Protected Against Solid Objects
Protected Against Water
Open Motors
IP00
Non-Protected Non-Protected Non-Protected
IP02
Non-Protected Non-ProtectedProtected against dripping water even when tilted 15� vertically
IP11
Protection against accidental contact with the hand Ingress of solid objects exceeding 50mm in diameter Protection against dripping water falling vertically
IP12
Protection against accidental contact with the hand Ingress of solid objects exceeding 50mm in diameter Protected against dripping water even when tilted 15� vertically
IP13
Protection against accidental contact with the hand Ingress of solid objects exceeding 50mm in diameter Protected against dripping water even when tilted 60� vertically
IP21
Protection against the touching with the finger Ingress of solid objects exceeding 12mm in diameter
Protection against dripping water falling vertically
IP22
Protection against the touching with the finger Ingress of solid objects exceeding 12mm in diameter Protected against dripping water even when tilted 15� vertically
IP23
Protection against the touching with the finger Ingress of solid objects exceeding 12mm in diameter Protected against dripping water even when tilted 60� vertically
Closed Motors
IP44
Protection against the touching with tools Ingress of solid objects exceeding 1mm in diameter Protection against splashing water from any direction
IP54
Protection against contacts Protection against accumulation of harmful dust Protection against splashing water from any direction
IP55
Protection against touches Protection against accumulation of harmful dust Protection against any water jets from any direction

For special and more dangerous areas where electric motors are required to be applied, the following degrees of protection are commonly used:
IPW 55 (Weather protection)
IP56 (Protections against water jets)
IP65 (Totally protected against dust)
IP66 (Totally protected against dust and water jets).

Tuesday, December 20, 2016

December 20, 2016

Basic Parts of a Three Phase (3-?) Squirrel Cage Induction Motor

The diagram below shows all the basic parts that makes up an AC induction motor. These basic parts work together to ensure the smooth performance of this highly efficient electrical device:
Parts of a three-phase Induction Motor - Photo Credit: WEG MOTORS

Stator Parts
As shown in the diagram above, the parts 1, 2 and 8 makes up the stator of the three-phase Induction motor:
1 � Motor Frame. This is the supporting structure of the motor assembly; manufactured        
     of  iron, steel, die-cast Aluminium, resistant to corrosion and with cooling fins.
2 � Lamination Core. This part is constructed with magnetic steel plates and houses the 
     motor windings.
8 � Three - phase Windings. This comprises three equal sets of coils, one se set for each 
     phase, forming a balanced three-phase system when connected to a three-phase        
     power supply.

Rotor Parts
The rotor of a three-phase squirrel cage Induction motor consists of a set of non-insulated bars that are interconnected by short-circuit rings. What characterizes an induction motor is the fact that only the stator is connected to the power supply. The rotor is not power supplied externally and the currents that flow through it are induced electromagnetically by the stator from which comes the induction motor name.

The parts 3, 7 and 12 makes up the rotor of the three-phase motor:
7 � Shaft. It transmits the mechanical output developed by the motor.
3 � Laminated Magnetic Core. The rotor laminations have the same characteristics of the       
     stator laminations.
12 � Rotor Bars and Short Circuit Rings. These are Aluminium die castings formed as one 
       piece. They enable the rotation of the motor through induction of electromagnetic 
       current 

Other Parts of The Motor
Below are listed other critical parts of the three-phase squirrel cage induction motor:
4 � End Shields
5 � Fan for cooling motor
6 � Fan Cover.
9 � Terminal Box. This houses the electrical terminals of the motor.
10 � Motor terminals
11 � Bearings. These support the rotation of the rotor.

Saturday, February 13, 2016

February 13, 2016

How to Measure Electric Motor Insulation Resistance


To prolong the life of electrical systems and motors, regular insulation resistance testing is required. Over the years, after many cycles of operation, electric motors are exposed to environmental factors such as dirt, grease, temperature, stress, and vibration. These conditions can lead to insulation failure, resulting in loss of production or even fires.


An effective motor insulation resistance system has high resistance, usually (at an absolute minimum) greater than a few mega ohms (M?).  A poor insulation system has lower insulation resistance. The optimal insulation resistance for an electric motor is often determined by the manufacturer�s specifications, the criticality of the application where the motor is used, and the environment where it is located.

It is practically impossible to
determine rules for the actual minimum insulation resistance value of an electric motor because resistance varies according to method of construction, condition of insulation material used, rated voltage, size and type. A general rule-of-thumb is 10 Megohm or more. The insulation system of an electrical motor is said to be in good condition if:
Measured Insulation resistance is greater than or equal to 10M?

Typical Insulation Resistance Level for Electric Motors
There are no rules for determining the minimum insulation resistance value for a motor. Most data available are empirical. The ones listed below are from grundfos, a leading manufacturer of electrical motors:

Insulation Resistance Level

Insulation Level

2M? or Less

Bad
2 - 5M? 
Critical
5 - 10M?
Abnormal

10 - 50M? 

Good
50 - 100M?
Very Good
100M? or More 
Excellent

How to Measure Insulation Resistance of a Motor
The measurement of insulation resistance is carried out by means of a mega ohmmeter � a high resistance range ohmmeter. To measure insulation resistance, a DC voltage of 500V or 1000V is applied between the windings and the ground of the motor as shown below:

During the measurement and immediately afterwards, do not touch any terminals of the motor as some of them carry dangerous voltages that may be fatal.
The minimum insulation resistance of motor measured to ground at 500V can be measured at a winding temperature of  -15�C � 20�C. The maximum insulation resistance can be measured at 500V with operating windings temperature of 80-120�C depending on the motor type and efficiency

How to Calculate Minimum Insulation Resistance of Motors
The minimum insulation resistance of any motor, Rmin, can be calculated by multiplying the rated voltage, VR, with the constant factor 0.5 M? /kV:
Rmin = 0.5*VR


Regular Checks of Motor Insulation Resistance The key to prolonging the life of any electrical device is periodic checks & maintenance. The insulation resistance of stored and active motors should be checked regularly:
(a)  If the insulation resistance of a new, cleaned or repaired motor that has been stored for some time is less then 10 M?, the reason might be that the windings are humid and need to be dried.
(b) For a motor in operation, the minimum insulation resistance may drop to a critical level. If the measured value of insulation resistance is greater than the calculated value of minimum insulation resistance, the motor can continue to run. However, if it drops below this limit, the motor has to be stopped immediately to prevent harm to personnel due to the high leakage voltage
February 13, 2016

How to Calculate Synchronous Speed and Slip of AC Induction Motors

Synchronous Speed
When Alternating current (AC) is applied to the stator of a three phase motor, a rotating magnetic field is setup. This rotating magnetic field moves with a speed called synchronous speed. The Synchronous speed can be calculated as follows: 120 times the frequency (F), divided by the number of poles (P):
The synchronous speed decreases as the number of poles increases. The table below shows the synchronous speed associated with various numbers of poles at supply frequencies of 50Hz and 60Hz:


No. of Poles Synchronous Speed @ 50Hz Synchronous Speed @ 60Hz
2 3000 3600
4 1500 1800
6 1000 1200
8 750 900
12 500 600

Rated Speed
The speed of operation of an AC motor when fully loaded at rated voltage is called the rated speed. It is usually given in RPM (Revolutions per minute) on an electric motor nameplate. The rated speed is the speed of the rotor.

Slip
The speed of the rotor magnetic field in an induction motor lags slightly behind the synchronous speed of the changing stator magnetic field. This difference in speed between rotor and stator fields is called slip and is measured in %.The slip  of an AC motor is a key factor and is necessary to produce torque. The greater the load (torque), the greater slip. The formula for calculating motor slip is given by:


Note that rotor speed is the same as the rated speed of the AC motor as given on the motor nameplate
February 13, 2016

How to Determine Electric Motor Overload Using Horse Power Rating

The electrical power supplied to an electric motor is converted into mechanical power for powering various loads such as pumps. The power output can be rated in KW (kilowatts)  or Horsepower (HP). In the United States, the mechanical output of the electric motor is rated in HP while elsewhere, it is in KW.
Note that:
1HP = 746W = 0.746KW
1KW = 1/0.746*HP = 1.34HP

Electric Motor Horsepower (HP)
Electric motor horsepower is dependant on speed and torque. When torque
is expressed in lb-ft and speed is expressed in RPM, the following formula can be
used to calculate horsepower (HP):

From the above formula, note that any increase in torque or speed or both increases horsepower.

How to Determine Output Horsepower Overload of an Electric Motor
To determine whether an electric motor is overloaded, we require:
(a)  The electrical power input
(b)  The efficiency of the motor or
(c)  The mechanical power output or horse power rating- This can be calculated or more accurately measured.

Electrical Power Input for Single and 3-Phase AC Motors:
For a single phase electric motor, power input is given by:
Power(Watts) = Voltage x Current x Power factor (P.F)

For a three phase AC motor, power input is given by:
Power(Watts)  = Voltage(line) x Current(line) x P.F x 1.732

Sample Scenario 1
Suppose we have a 1HP, single phase motor with power factor of 75% and efficiency 90% and is driving a fan. If the voltage and currents are respectively 123V and 10Amps, is this motor overloaded?

Let us first compute Electrical power input to motor as shown above:
Power input = Voltage x Current x P.F
                   =  123 x 10 x 0.75 = 922.5W
In horsepower we have = 922.5/746 = 1.24HP
Now we already know the electrical power input of the motor which is = 1.24HP
With an efficiency of 90%, power output is calculated thus:
Efficiency = Mechanical power output (HP)/Electrical power input(HP)
Mechanical power output = Efficiency x Electrical power input (HP)
                                       = 0.90 x 1.24 = 1.12HP

This motor is definitely overloaded!


Sample Scenario 2
A 10HP, 400V, 3-phase AC motor with power factor of 80%  and efficiency 85% takes in an average current of 16.5 Amps and is driving a pump load. Is this motor overloaded?

The electrical power input to the 3-phase AC motor is given by:
Electrical power input = Voltage x Current x P.F x 1.732
                                  =  400 x 16.5 x 0.8 x 1.732 = 9,144.96W
In horsepower is          =  9144.96/746 = 12.26HP

Motor power output = Efficiency x Electrical input
                               = 0.9 x 12.26 = 11.034HP



Again, this AC motor is overloaded!

In general, if:
The calculated or measured power output of an electric motor in horsepower(HP) is greater than the nameplate rating, then the motor is evidently overloaded!

Friday, February 12, 2016

February 12, 2016

Insulation Classes for Electric Motors

NEMA motor insulation classes describes the ability of motor insulation in the windings to handle heat. There are four insulation classes in use namely: A, B, F, and H. All four classes identify the allowable temperature rise from an ambient temperature of 40� C (104� F). Classes B and F are the most common in many applications.

Temperature rises in the motor windings as soon as the AC motor is started. As shown in the table below, the combination of ambient temperature and allowed temperature rise equals the maximum rated winding temperature. Allowable temperature rise is made up of the maximum temperature rise for each insulation class plus a hot-spot over-temperature allowance. If the motor is operated at a higher winding temperature, service life will be reduced. As a rule,
a 10� C increase in the operating temperature above the allowed maximum can cut the motor�s insulation life expectancy in half.
The table below shows the different insulation classes as defined by NEMA:
Class Maximum Ambient Temperature (�C) Maximum Temperature Rise (�C) Hot-spot Over Temperature (�C) Maximum Winding Temperature (Tmax)(�C)
A 40 60 5 105
B 40 80 10 130
F 40 105 10 155
H 40 125 15 180

Hot-spot Over Temperature Allowance
Each insulation class has a margin allowed to compensate for the motor�s hot spot. The hot-spot is a point at the center of the motor�s windings where the temperature is higher. As can be seen from the above table, hot-spot over temperature allowance for A, B, F and H are respectively 5�C, 10�C, 10�C and 15�C

When replacing a motor, extreme care must be taken not to choose a motor with the wrong insulation class. It is advisable therefore to replace a motor with one having an equal or higher insulation class. Replacement with one of lower temperature rating could result in premature failure of the motor.
February 12, 2016

Speed -Torque Characteristics of Polyphase Electric Motors

Understanding the relationship between the load carried by an AC motor and the torque it develops during each stage of operation of the motor is crucial to selecting the right kind of electric motor for the right kind of application. AC Motors are therefore designed with torque-speed characteristics to match the requirements of common applications. The four standard NEMA motor designs, A, B, C, and D, have different characteristics. Below shows a typical torque/speed curve for an AC motor:

An AC motor develops four basic types of torques during operation. They are:

(a) Starting Torque (ST)/Locked Rotor Torque (LRT)
(b) Pull-up Torque (PUT)
(c) Breakdown Torque (BT)
(d) Full Load Torque (FLT)

Starting Torque/Locked Rotor Torque
Starting torque, also referred to as locked rotor torque, is the torque that the motor develops each time it is started at rated voltage and frequency. It is the torque produced when power is applied to a motor at rest, i.e. when the motor is energised at full voltage and the shaft is locked in place. This is the torque used to start accelerating the load. The starting torque is indicated on the torque/speed curve shown above.

Pull-up Torque (PUT)
This term is used for the lowest point on the torque speed curve for an electric motor which is accelerating a load up to full speed. As the motor picks up speed, torque decreases slightly to the lowest point shown on the curve above. The torque available at this point is called pull-up torque.

Breakdown Torque (BT)
Breakdown torque is the maximum torque that an AC motor develops with rated voltage applied at rated frequency without causing sudden drops in speed. This is also known as pull-out torque or maximum torque.

Full-Load Torque (FLT)
The torque required to produce rated power at full-load speed. Full-load torque is developed with the motor operating at rated voltage, frequency, and load. At full-load torque, the speed of the electric motor is slightly less than the synchronous speed as shown in the curve above.
February 12, 2016

NEMA Three Phase Electric Motor Designs

Three phase induction motors are specified by their electrical design type. NEMA  (National Electrical Manufacturers Association) has classified three phase AC motors into design A, B, C, D. A more recent design called E has been added. These designs are suited to particular classes of applications based upon the load requirements typical of each class.

As a motor operates from no load to full load, its torque varies with speed. The relationship between speed and torque is often shown in a graph, called a speed-torque curve. This curve shows the motor�s torque, as a percentage of full-load torque, over the motor�s full speed range, shown as a percentage of its synchronous speed. NEMA classification is based on the speed-torque curves. Typical speed-torque curve for designs A, B, C, and D is shown below:



Characteristics of NEMA Three phase Motor Designs

NEMA Design A Motors
The table below shows the typical characteristics of all NEMA A Motors:

Basic Characteristics
  • High locked rotor torque
  • High locked rotor current

Locked Rotor Torque (% of Full-load Torque)

70 - 275%

Pull - Up Torque (% of Full-load Torque)
65 - 190%

Breakdown Torque (% of Full-load Torque)

175 - 300%
Locked Rotor Current (% of Full-Load Current)
 -

Slip

0.5 - 5%

Areas of Application
Fans, blowers, centrifugal pumps
and compressors, motor-generator sets, etc., where starting torque requirements are relatively low
Efficiency High or Medium


NEMA Design B Motors
The table below shows the typical characteristics of all NEMA B Motors. NEMA design B motor is the most common three-phase AC induction motor design.

Basic Characteristics
  • Normal locked rotor torque
  • Normal locked rotor current

Locked Rotor Torque (% of Full-load Torque)

70 - 275%

Pull - Up Torque (% of Full-load Torque)
65 - 190%

Breakdown Torque (% of Full-load Torque)

175 - 300%
Locked Rotor Current (% of Full-Load Current)
 600 - 700%

Slip

0.5 - 5%

Areas of Application
Fans, blowers, centrifugal pumps
and compressors, motor-generator sets, etc., where starting torque requirements are relatively low
Efficiency High or Medium


NEMA Design C Motors
The table below shows the typical characteristics of all NEMA C Motors:

Basic Characteristics
  • High locked rotor torque
  • Normal locked rotor current

Locked Rotor Torque (% of Full-load Torque)

200 - 285%

Pull - Up Torque (% of Full-load Torque)
140 - 195%

Breakdown Torque (% of Full-load Torque)

190 - 225%
Locked Rotor Current (% of Full-Load Current)
 600 - 700%

Slip

1 - 5%

Areas of Application
Conveyors, crushers, stirring
motors, agitators, reciprocating
pump and compressors, etc.,
where starting under load is
required
Efficiency Medium


NEMA Design D Motors.
The table below shows the typical characteristics of all NEMA D Motors:

Basic Characteristics
  • Normal locked rotor torque
  • High slip

Locked Rotor Torque (% of Full-load Torque)

275%

Pull - Up Torque (% of Full-load Torque)

-

Breakdown Torque (% of Full-load Torque)

275%
Locked Rotor Current (% of Full-Load Current)
 600 - 700%

Slip

5 - 8%

Areas of Application
High peak loads with or without
flywheels such as punch presses,
shears, elevators, extractors,
winches, hoists, oil-well pumping
and wire-drawing motors
Efficiency Low


NEMA Design E Motors
This is the newest NEMA design category. Below are the typical characteristics of  NEMA E motors:

Basic Characteristics
  • Normal locked rotor torque
  • Normal locked rotor current
  • Low slip

Locked Rotor Torque (% of Full-load Torque)

75 - 190%

Pull - Up Torque (% of Full-load Torque)

60 - 140%

Breakdown Torque (% of Full-load Torque)

160 - 200%
Locked Rotor Current (% of Full-Load Current)
 800 - 1000%

Slip

0.5 - 3%

Areas of Application
Fans, blowers, centrifugal pumps
and compressors, motor-generator
sets, etc., where starting torque
requirements are relatively low
Efficiency High
February 12, 2016

What is AC Motor Service Factor (S.F) Rating?

The service factor (SF) of an AC motor  is a measure of continuous overload capacity at which a motor can operate without overload or damage, provided the other design parameters such as rated voltage, frequency and ambient temperature are within the manufacturers� specifications.

Motor service factor is crucial in determining the overload capacity of any given motor. The maximum load an AC motor can carry without overheating or otherwise damaging the motor if rated voltage and frequency are supplied at the motor�s leads is given by:


Maximum  Load  Capability of Motor = S.F x Rated or Nameplate Horsepower Rating
For example, the maximum motor load for a 1HP electric motor with a service factor of 1.15 is :
=  1.15 x 1 = 1.15HP
Anything above this load will certainly result in motor overheating and consequent damage of the AC motor.

Typical Service Factors (SF) for AC motors.
In the U.S, the defacto standard for AC motors is the NEMA standards. For totally enclosed motors (TEFC), the standard NEMA service factor is usually 1.0. Many manufacturers of TEFC motors often manufacturer motors with service factor of 1.15.  Below are typical service factors for Drip Proof Motors (DPM):
Horsepower Rating (HP) Service Factor(SF)/Synchronous Speed (RPM)
3600 1800 1200 900
1/6 , 1/4, 1/3 1.35 1.35 1.35 1.35
0.5 (1/2) 1.25 1.25 1.25 1.25
0.75 (3/4) 1.25 1.25 1.15 1.15
1.0 1.25 1.15 1.15 1.15
1.5 (1,1/2) or greater 1.15 1.15 1.15 1.15

Service Factor (S.F) Versus Motor Replacement
As seen above, the maximum load capability of an AC motor is = S.F x Nameplate Hp rating. Given this, never make the mistake of replacing an electric motor with the same horse power rating but with a lower service factor! It is recipe for disaster!
Rather when replacing an AC motor, the rule of thumb as far as service factor is concerned is:
NEW Motor MUST HAVE a maximum HP rating (= S.F x Rated or Nameplate HP) equal to or greater than that of the OLD Motor (bad motor) being replaced.

Thursday, December 24, 2015

December 24, 2015

Temperature Classifications for AC Motors Application

When an electric motor is used in an atmosphere with explosive gas, the motor  surface might become hot enough to cause auto-ignition.  Auto-ignition temperature is the temperature at which a gas will ignite spontaneously without any other source of ignition. When hot surfaces are in contact with an explosive atmosphere, auto-ignition is likely to occur.

The table below gives the classification, which is used to indicate the maximum surface temperature that a given piece of an electric motor (the table is for motors designated as EExd) can reach when it is running normally. In general applications, the maximum surface temperature is based on a surrounding temperature of 40�C. The motor�s T-classification can be compared with the auto-ignition temperature for gases. The T-classification helps in making the right decisions regarding the AC motor�s use in areas with explosive atmospheres:


Temperature Class
Maximum Surface Temperature
Groups of Gases
IIA
IIB
IIC
T1
450�C
Methane, Ammonia
Hydrogen
T2
300�C
Butane
Ethylene
Acetylene
T3
200�C
Kerosene, Cyclohexane


T4
135�C
Acetaldehyde
Diethyl
Ether

T5
100�C



T6
85�C


Carbon
Disulphide

Groups of Gases and Vapors
Gases are divided into the following two explosion groups depending on which kind of industry the motor or equipment is to operate in: Explosion group I and II.
Explosion Group Industry Specified
Group I Mines and other underground industries
Group II Off-shore industries and industries above ground


Explosion Group II Gases
Explosion group II is divided into three subgroups, IIA, IIB and IIC. Some typical gases in these groups are shown in the table below:
Typical Gas Hazard Gas Group
Acetylene IIC
Hydrogen IIC
Ethylene IIB
Propane IIA
Methane I (firedamp) mining, IIA industrial

As shown above, the danger of gas explosion increases from group IIA to group IIC. IIC is considered the most dangerous explosion group. The higher the dangers of explosion, the stricter are the requirements to the AC motor required to be used in these explosive environment. Therefore, it is mandatory that electrical equipment required for use in hazardous environment carries a clear marking of what explosion group it belongs to

Wednesday, December 23, 2015

December 23, 2015

How To Test Three - Phase AC Motors

The basic steps in ascertaining the health of a three-phase AC motor are given below:
(a) General Inspections
(b) Earth Continuity and Resistance Test
(c) Power Supply Test
(d) AC Motor Winding Continuity Test
(e) AC Motor Winding Resistance Test
(f) Insulation Resistance Test
(g) Running Amps Test

General Inspections
For the three-phase motor, do the following:

(1) Check the appearance of the motor. Check for burnt, damage to body or cooling fan or shaft.
(2) Manually rotate motor shaft to examine bearing condition. Look out for smooth and free shaft rotation. If shaft rotation is free and smooth, bearing is possibly in good condition, otherwise consider replacing, repair or carry out further diagnosis.
(3) As with all testing and inspections, the motor name plate provides valuable information that will help to ascertain the true health of the motor. Examine the name plate thoroughly and compare values of running amps test (see below) with name plate value

Earth Continuity and Resistance Test
With a multimeter, measure the resistance between motor frame (body) and earth. A good motor should read less than 0.5 ohms. Any value greater 0.5 ohms indicate trouble with the motor. Further troubleshooting maybe required

Power Supply Test
For three phase motors, the expected voltage for a 230/400V system is 230V phase to neutral and 400V between each of the three phase supply lines. Check that the correct voltage is applied to the motor using a multimeter.  Ensure the terminal for power supply is in good condition. Check the connection bar for terminal (U, V, and W). For three phase motors, connection type is either Star (Y) or Delta

AC Motor Winding Continuity Test
Using a multimeter, check the continuity of motor winding from phase to phase ( U to V, V to W , W to U ).Each phase to phase must have a continuity if winding is OK. If any particular phase fails the continuity test, your motor is probably burnt.
Please see how to identify three phase windings for proper winding identification. U, V, W is a European winding designation.

AC Motor Winding Resistance Test
Check the motor winding resistance or ohms reading using a multimeter or ohmmeter for phase to phase terminal ( U to V,V to W ,W to U ).The ohms reading for each winding must be the same (or nearly the same). Remember that the three phases have identical windings or nearly so!

Insulation Resistance Test
Insulation resistance failure of an electric motor is one of the first signs that the motor is about to fail. For a three phase motor, insulation resistance is usually measured between each motor winding or phase and between each motor phase and motor frame (earth) using an insulation tester or megger. Set the voltage setting of the insulation resistance tester to 500V.  Check from phase to phase (U to V, V to W, W to U). Check from phase to motor frame (earth) (U to E, V to E , W to E ). Minimum test value of motor insulation resistance is 1 Meg Ohm (1 MO). See how to measure insulation resistance of Electric Motor

Running Amps Test
With the motor running, check the full load amps (FLA) with a suitable meter or preferably a clamp on meter and compare with the name plate FLA. Deviations from rated FLA could signify problems with the motor under test.